10-061
 Click to Zoom
The Wi-Fyre Wireless Input/Output Module has been designed to provide a means to trigger an alarm or fault from ancillary input operations and/or to switch remote equipment in the event of an alarm condition. When operating together with a transponder set to mode 5, it can also be used as a reflective input/output device to wirelessly interconnect two or more stand-alone fire alarm panels together.

The Wi-Fyre Wireless Input/Output Module has been designed to provide a means to trigger an alarm or fault from ancillary input operations and/or to switch remote equipment in the event of an alarm condition. When operating together with a transponder set to mode 5, it can also be used as a reflective input/output device to wirelessly interconnect two or more stand-alone fire alarm panels together.

Specifications
- Operating Frequency: 868 - 870 MHz, 14dBm
- Range: 150m open area
- Power Source: 4 x Lithium AA Cell (Saft LS14500); 2 x Lithium C Cell (Saft LS26500)
- Battery Life: Up to 3 years
- Input End-of Line: Normal = 22k Ohm, Alarm = 1k Ohm
- Manual Alarm Relay Contact: 1 x Solid-state normally open, 60Vdc, 600mA
- Automatic Alarm Relay Contact: 1 x Solid-state normally open, 60Vdc, 600mA
- Common Fault Contact: 1 x Solid-state normally closed (failsafe), 60V, 500mA
- Dimensions (Diameter x Height x Depth): 122 x 128 x 50mm
- Weight (Including Batteries): 460g
- Housing Material: ABS
- Colour: Red
- Tamper: Yes
- Applicable Standards: EN54-25, BS 5839 Part 1:2002, ENTSI 300:220