EVC302F
 Click to Zoom
Brushed Stainless Steel Disabled Refuge Outstation, flush

Specifications:
Approvals/certifications: Facilitates compliance with BS5839-9 when correctly installed.
Supply/operating voltage : 11V DC derived from a compatible SigTEL Master Controller (drops to 6 V DC when in use).
Quiescent current: 3mA
Activation current: 25mA (current draw when intercom is in use).
Open collector outputs: O/P +Ve & O/P –Ve (closes when outstation is active, typically used to trigger a third party CCTV camera, opto-isolated, normally open, max. 24 V DC, 3 mA).
Indicators: Red call in progress LED
Controls: External 'Push to Call or Answer' button (Off Hook); Internal Loudspeaker volume control; Engineer’s “On Hook” and “Off Hook” pins.
Expansion connections: AFILS +Ve & AFILS –Ve (typically connected to the line-level input of an optional induction loop amplifier): Off-Hook and -Ve (can be optionally connected to an NC951 accessible toilet alarm kit
Product dimensions (mm): 175 W x 250 H x 53 D mm. Hole required for flush mounting: 156 W x 232 H x 51mm D approx (no bezel required).
Construction & finish: Brushed stainless steel.
IP Rating: IP20.
Weight: 1.5 kg.
Operating conditions/temperature: -5ºC to +40ºC. Max relative humidity: 95%.

Notes
Microphone frequency response 250 Hz to 5 kHz ±3 dB; Loudspeaker frequency response 250 Hz to 4 kHz ±3 dB; Audio output level: 0 dB (775 mV) balanced line.